1. Main performance index

No.

Project

Parameter

1

AC voltage and current sampling accuracy

0.2 grade

2

Active and reactive sampling accuracy

0.5 grade

3

Frequency sampling accuracy

0.01Hz,Sampling range 45Hz~65Hz

4

Fault current input range

10In

5

Input circuit

Optical isolation

6

Contact voltage

24VDC

7

SOE Resolution

5ms

8

Remote signaling transmission time during accident

<1S

9

Software anti-shake time

0~60000ms can be set randomly

10

Power consumption

<30W


2. Main function

◇Collect Ua, Ub, Uc, Ia, Ib, Ic, Fr, P, Q, S and other analog quantities

◇Telemetry             ◇Remote control            ◇Remote communication

◇Parameter setting       ◇Terminal self-test          ◇Data storage

◇Fault detection         ◇Telemetry limit detection    ◇Communication

◇Debugging